Classroom Core Standards
- Frank Gonzales
- Nicole
- Mitashi Parikh
Classroom Technology Standards
The Classroom Technology standards document represents the latest standards for University Scheduled Classrooms on campus. This document is meant to be handed off to building architects, contractors, and individual departments when looking at standards, processes, and ideal room setups conducive to a great classroom experience for all users of the space (presenters, students, and technical support staff, custodial support staff) with the most weight put on the learner's experience.
CSI MasterFormat
Construction Standards Reference Section
27 41 16.51 - Integrated Audio Video Systems and Equipment for Classrooms
Telecommunications Infrastructure Planning (TIP) Standards
This document provides the minimum standards governing the development of technology resources and infrastructure across the CSU system.
Cal Poly ITS Telecommunications Standards
This document provides the minimum standards governing the development of technology resources and infrastructure at Cal Poly, building upon TIP and applying to the specific needs of the campus.
Cal Poly ITS Classroom Technology Standards
This document provides the minimum standards governing the development of technology resources and infrastructure at Cal Poly, building upon TIP & Cal Poly Telecommunication Standards and applying to the specific needs of the campus.
Visit the Telecommunications page for more information.
Learning spaces should be designed from the “inside-out,” such that the function and the purpose of the classroom are the number one priority of design, not building mechanical systems. Refer to Room Design Considerations below.
Learning spaces should incorporate capabilities to support flexibility of use; furniture, function, collaboration, and technology. Increased square footage allotted for students increases the degree for classroom flexibility.
Classroom design elements should be inviting to students; breaking away from an “institutional” feel that has dominated classroom design for decades. The classroom may be configurable such that any wall could be a presentation area.
Learning spaces may incorporate formal and informal learning areas such as meeting spaces, seminar spaces, lecture spaces, conference rooms, and traditional classrooms.
Audio-Visual System design and installation contractors shall have a minimum of 1 AVIXA CTS-D certified member and a CTS-I certified member.
Audio–Visual System infrastructure and components should be reflected in dedicated page(s) in architectural plans, including elevations and mounting details.
Audio–Visual System infrastructure and components should be reflected in Electrical, Telecomm, and Mechanical architectural plans.
All architectural plans that involve learning spaces or audio-visual technology elements shall be commented on during the design phase and approved by Cal Poly ITS Operations representative and classroom designer to ensure conformity to university standards and functionality needs.
Note viewing angles and screen dimensions on construction documents.
Finished ceiling height should be a minimum of 10’ above finished floor in instructional spaces.
Student seating areas should fall within the basic decision-making model range (Powerpoint viewing) based on AVIXA’s V202.01:2016 Standard for Display Image Size for 2D Content in Audiovisual systems
Screen heights should observe a maximum 30-degree vertical angle between the horizontal line at eye level and the top of the image to minimize extended viewing neck strain. (Typically bottom of display image should be no lower than four feet AFF.) Refer to AVIXA’s V202.01:2016 Standard for Display Image Size for 2D Content.
Image size must be based on the Basic Decision Making model in AVIXA’s V202.01:2016 standard with compensation made for ceiling heights by introducing additional displays to ensure minimum visual strain to students. Use of older rule-of-thumb guidelines must not be used, such as the 4-6-8 rule.
The closest student seats to the presentation display screen should be based on Basic Decision Making (BDM) model in AVIXA’s V202.01:2016 standard with compensation and allowance made for CSU or Cal Poly Scheduling seating density requirements.
Student’s ability to access power for mobile devices should be incorporated into classroom designs. Typically place electrical outlets around the classroom perimeter every 5 feet or as necessary to allow for 30% utilization. All outlets must be within ADA guidelines for reach (i.e. 18" AFF).
Classroom lighting should be recessed for rooms with a drop tile ceiling and not incorporate any hanging fixtures.
Classroom lighting should be grouped into lighting zones with controls near the instructor area that allow the instructor to turn on/off lighting within the zones.
Classroom lighting systems must provide an interface and API to connect to the classroom AV control system
Classroom lighting scenes and presets based on zones must be created, and that type of information must be documented as part of the classroom configuration documentation
Classrooms specifically designated for distance learning must follow IES/AVIXA RP-38-17 video conferencing lighting standard
If there are wall-mounted projectable whiteboards, the same wall should have a dark color to improve the contrast of the projected image. If it is used in a distance learning scenario with a remote presenter, the wall behind the students should also be a neutral to darker color.
Learning spaces should be free of any structural elements (posts, beams, pillars, hanging lights, walls, room angles, etc…) that hinder the sightlines of students.
Learning spaces should incorporate generous amounts of usable whiteboard surfaces. A minimum of 10’ of linear whiteboard space on the same horizontal plane should be available for usage while projected images are in use.
Audio–Visual system design and components shall be approved by a Cal Poly ITS Operations representative, typically the Classroom AV engineer; incorporating approved “standard” equipment elements, incorporate robust wireless networking, sufficient to incorporate the increasing demand of mobile.
If a Classroom Audio-Visual system must be designed in a way that does not meet the current Cal Poly ITS Classroom standard, the reason for the deviation must be clearly documented and must receive ITS approval before any purchases are made.
Audio–Visual Contractor submittals shall include: Parts list, shop drawings including rack layout diagrams, cable lists, and line-diagrams, post-project as-built drawings, equipment specification sheets, and warranty information.
All Audio–Visual cables and connections shall be labeled at both ends of the cable following the AVIXA F501.01:2015 standard. Cal Poly utilizes two lines for cable labels, a Cable ID, and a Cable source to destination description.
Classroom design should seek to incorporate energy-saving “green” audiovisual features based on AVIXA’s ANSI 4:2012 Audiovisual Systems Energy management standard as well as “green” cradle-to-cradle construction elements.
Classroom design must follow environmental guidelines for lighting levels; ambient noise levels—both HVAC and ingress; acoustic treatment. Refer to the section below: Acoustics and Environment.
When planning for AV in new buildings, especially ones that include university scheduled classrooms, an Architect and AV consultant must coordinate with the ITS standards document and AV designer and include ITS in all early budgetary discussions, programming phase charrettes and planning, and post-programming drawing reviews of construction drawing sets.
Final Audio-Visual equipment selection and system design shall be coordinated with campus representatives. Due to the rapidly changing technology horizon; standardized equipment and system design selections should be made as close to building commissioning as possible to ensure the most up-to-date technology is available.
It is required to acoustically treat rooms to optimize STI (sound transmission index) to prevent transmission of both the vocal frequency range between rooms and low frequencies). New build out of classrooms requires walls built up to the deck, staggered studs between gypsum boards, and acoustic sound batting between gypsum board. Rubber baseboard molding needs to be acoustically rated along with any glue used. Ceiling tiles must be acoustically rated as well, and we recommend the use of reclaimed denim insulation to improve noise reduction coefficient rating.
Any conflicting standards presented, the more stringent standard must be used or referred to the AHJ (authority-having-jurisdiction)
A. Media Junction Box
Intent
Centralized landing zone for all wiring, power, and connections required between a presenter's station and the wall which will be serviced by the campus data network, building AC power, data ports designated for audio-visual content and control transport, disconnect point for any ceiling speakers, and general disconnect point for any additional cabling needed to go out to the rest of the room and any AV rack(s).
Specifications
Media Junction Box shall be wall recessed, flush with finished wall or finished floor. A typical size is 14” x 24” x 4”. The media box should be designed to fit between studs in the wall. Media box shall have a screw or locking cover door with flush locks and cable entry access to connection panels. Media Box shall be white or painted to match wall color. Media box shall contain AC power, networking, and media connection faceplates. High voltA. age dividers must be used to separate AC power from low voltage signal areas. Media box shall have a minimum of (1) - 2” or (2) - 1.25” ‘home run conduits’ from the media box to the plenum pull-box continuing 1.25” conduit to display location as appropriate. Media box shall have a minimum of one (1) 1.25” conduit ‘home run’ to the nearest network cable tray.
Specified Product(s)
Legrand EN2850 or Approved Equal
Additional Details
Media box shall be serviced with: electrical, network, & Audio, Video and Control low-voltage connectivity (typical). Refer to Appendix for layout details. Refer to Installation Cable section below for cable details. Slanted-style Keystone faceplates are desired to mitigate bends in CAT6 a cables.
1. Electrical
120 VAC, 20A [dedicated] service, 2 outlets
2. Network Data, Video, Power-Over-Ethernet (POE IEEE 802.3bt)
CAT6 UTP (Data)
Shielded CAT6a (Video) HDBT certified.
Keystone RJ45 jacks must be shielded.
3. Audio and Control
Loudspeaker: Two or four-conductor, 16 AWG STP, plenum
One pair Keystone banana jacks termination for every 8-Ohm loudspeaker
One pair Keystone banana jacks termination for 70-Volt loudspeaker distribution
Shielded, twisted pair (STP): Single pair, 22 AWG stranded, shielded, plenum
4. Voice
CAT6 UTP for VoIP applications
B. Wall Chase
Intent
In the event that the Media Junction Box and associated conduit cannot be installed recessed within the wall depth, an alternative floor-to-ceiling solution can be used. This has the same purpose as the Media junction box, to be a cable landing zone for classroom and building services related to technology components
Specifications
A framed chase should be constructed to enclose the Junction Box/conduit from floor to ceiling and painted to match the adjacent wall. This is a large, square chase in anodized aluminum with a furniture feed, device cover plate with three mini-adapter openings, and access door (latching, no locks). See Media Junction Box Detail below for illustration.
Specified Product
The Legrand Vista Architectural Column VFL77 2345CM GY D, or Approved Equal.
Media Junction Box Detail
C. AV Break-Out-Box (BOB) Junction Box
Intent
The BOB Junction box is meant to house a 2-Gang HDBaseT transmitter that can be used to facilitate a hardwired connection for a digital video cable (HDMI) from the outside, and be connected via a single CAT6A junction on the inside of the junction box. This is a surface mounted box for environments where a recessed box is not feasible.
Specification
The ‘BOB’ junction box shall be a surface mounted 2- gang, 4 3/4" (121mm) x 4 3/4" (121mm) x 2 3/4" (57mm) deep box with a 1-¼” conduit pathway ‘home run’ to the media junction box. It should be co-located near user data and electrical outlets. All BOB connections are low-voltage. The junction box will house the wall plate/interface (an HDBT transmitter)
Specified Product
Wiremold Part# V5744-2 in Ivory or Approved Equal
Additional Connectivity/Cabling Requirements
Shielded, CAT 6 cabling (HDBT-certified) terminated with shielded, female RJ-45 key stone jacks.
STP cable, single pair, unterminated
D. Floorbox
Intent
Floorboxes are typically used to provide AC outlets, AV connections, and LAN connections to a podium or table. Multiple floorboxes in a room can be used to enable relocating the instructor station or in active learning scenarios, infrastructure connection points for group tables/pods.
Specifications
Floor box shall be suitable for raised concrete floor applications. The floor box shall contain minimum for (4) 1-1/4” knockouts and have serviceable gang- sized mount plates with dividable sections for power data and audio-visual connections. Hinged cover plate should allow for attached cables to exit without damage.
Specified Product
FSR Part# FL-500 series or Approved Equal; Cover panel t.b.d.
E. Over-the-floor Cable Raceway
Intent
Raceway is used for any cable(s) that needs to run openly between a wall and across an unobstructed the floor for more than 12 inches to a mobile display, podium, or table.
Specifications
Raceway must meet ADA ramp guidelines and all building codes. Must be suitable for installation in any floor type. AV, Power, and Data should run through separate channels in raceway. Cables in raceway must be easily accessible via a removable cover
Specified Product
ConnectTrack 2.7 On Floor Wireway or Approved Equal
F. Ceiling Equipment Storage Box
Intent
Ceiling box is used to discreetly place equipment in ceiling, typically above where a display is mounted. Equipment stored in the box could include an audio amplifier or an HDBaseT receiver.
Specifications
Ceiling junction box shall be plenum-rated false ceiling equipment storage. Projector ceiling box shall fit in “T-Bar” type 2’x2’ or 2’x4’ drop ceiling grids or similar cutouts in hard lid applications. Projector ceiling box shall contain a minimum of 4 electrical outlets, one exposed on ceiling surface specifically for the projector. Projection Box shall contain fully terminated Media Connection Faceplate from Media Connection Box. Projector ceiling box shall contain 2 rack units of space inside enclosure with optional exhaust fan and have locking door accessible from below finished ceiling. Projector ceiling box shall provide 1.5” NPT threaded fitting to allow for mounting a projector. Ceiling Box shall have adequate seismic safety cabling and shall be anchored to the ceiling top deck, minimum of 4 anchor points. All mounts shall be installed according to manufacturer’s specifications and campus guidelines .
Specified Product
Premier Mounts Part# GB-AVSTOR3/GB-AVSTOR5 or Approved Equal
G. Display Ceiling Mount for Ceiling Tile Replacement
Intent
Projector ceiling mount attachment that drops into ceiling tile grid is used in situations were mounting directly to the deck is problematic. Will still need to be tethered to structural supports.
Specifications
Projector ceiling mount shall be plenum-rated, full-tile false ceiling adapter with quick-lock cables which replaces a 24 inch (610 mm) x 24 inch (610 mm) ceiling tile. Mount shall feature two or more electrical and cable knockouts for running power or signal. Accepts a 1.5 inch (38 mm) NPT pipe and uses wingnuts for rapid projector adjustments. The mount also has the ability to shift the display or projector by 4 inches (102 mm) in any direction. All mounts shall be installed according to manufacturer’s specifications and campus guidelines . All mounts shall have adequate seismic anchors and a minimum of 4 anchor points.
Specified Product
Premier Part# PP-FCMA-QL/GB-AVSTOR 5 or Approved Equal
H. TV Box
Intent
To efficiently manage cables behind a wall-mounted display for appropriate wall types.
Specifications
TV Box shall install in-between 2 standard wall studs in wall cavity flush to finished wall.
TV Box shall contain 2 low voltage back boxes and 2 UL listed Gem boxes.
Box shall contain one (1) 120 VAC duplex outlet, 2 CAT6 network drops [home run to cable tray, 1-1/4” conduit].
TV Box shall contain 1-1/4” conduit to AV pull box (ceiling above TV) and 1-1/4” conduit to 3 gang double deep box at 10” A.F.F. (below TV); for conference rooms, AV pathway shall continue to conference table location.
TV Box Shall contain mounting for AV connection modules.
Specified Product
FSR Part# PWB-100 or Approved Equal
I. Loudspeaker Back Box
Specifications
Speaker back box shall contain seismic wire safety connection, ¾” conduit connections with whip and sufficient speaker cable to allow for installation and servicing. In most cases, the back box is an integral part of the specified ceiling loudspeaker.
Specified Product
JB L Part# Control-26C; Extron Part# CS120P, SM26, or Approved Equal
J. EMT Conduit
Requirements
All conduits shall be continuously bonded back to the TGBB (telecommunication grounding bus bar) in the TR/ER (telecommunication room/electrical room).
All Audio/Visual Conduits must be (1) 2” or (2) 1-¼ ” between Media Connection box and above ceiling junction box. minimum (1) 1-¼" conduit to each display location.
Audio/Visual Conduits used only for two pair of two-conductor 14AWG speaker wiring can be 1" in diameter.
All conduit terminations will be equipped with bushings.
All conduits shall contain a pull string.
Conduits run for horizontal cabling shall not be installed below a building’s slab; however, they may be installed within the slab.
The maximum allowable pulling force on a 4-pair cable or bundle of cables is 25 lbs. Over-filled conduit, long conduit runs and bends increase the pulling force required to pull the cable.
Conduit Bends
There should be no more than two 90-degree bends (or combination of bends equaling 180 degrees) between pull boxes or pull points.
For reverse bends (between 100 and 180 degrees) insert a pull box at each bend.
The recommended 90-degree bend radius for conduit is 6 times the internal diameter of the conduit; 10 times the internal diameter if the conduit is larger than 2 inches.
Conduit runs should contain no continuous sections longer than 100 ft. without a pull box.
All firewall penetrations will be sleeved and fire-stopped.
Pull Boxes
Pull boxes shall not be used in lieu of a 90-degree bend, and conduits should be aligned such that pulls are straight through with no jogs.
Pull boxes should be located such that conduit runs do not exceed 100 feet.
Minimum size for pull boxes; length should be 8x diameter of the largest entering conduit; width should be 4x the diameter of the largest entering conduit.
If the pull box will require a faceplate with an integrated CAT6 connector, the box depth must allow for an internal cable radius; typically, a 4-11/16” deep box with a 1-1/4” conduit pathway and preferably using a side cable entry.
Where possible, 6-ft. cable service loop(s) should be secured with Velcro-type fasteners above the projector ceiling plate. Zip-ties should never be used on Category cable.
K. Projection Screens
Motorized screens
Projection Screen wider than 7 feet shall be motorized.
Specifications
Projection screen fabric shall have a matte white projection surface (1.0 gain) with black borders if audience falls within viewing angle of screen.
If audience falls within the narrower band a gray "HD" screen (1.2 or 0.8 gain) may be used for the projection screen fabric with black borders.
Motorized Screen stop point shall be four feet about finished floor in most situations, exceptions must be reviewed with ITS AV designer and/or client(s).
Screen shall not cover any building system sensors, clocks, or fire alarm flashers.
Recessed screen housing should be separate from any ceiling gird system, allowing for replacement and servicing of screen without damaging ceiling materials. Seismic cables are required , minimum of 4 anchor points.
Screen location must take into account viewing angles, the closest and furthest viewer, and minimize coverage of whiteboards. Refer to Appendix.
Screen control shall below voltage switch and be mounted close to the user area.
Screens must be installed according to manufacturer’s specifications and campus standards.
Specified Product
Da-lite Cosmopolitan Electrol or Approved Equal
Manual Screens
Manual projection screens over seven feet in width shall not be used.
Projection screen shall have a matte white projection surface with black borders. Screen stop point shall be four feet about finished floor. Screen shall have slow retraction mechanism. Screen shall not cover any building system sensors, clocks, or fire alarm flashers.
Recessed screen housing should be separate from any ceiling grid system, allowing for replacement and servicing of screen without damaging ceiling materials.
Wall-mounted screens should use a wall mounting board, 1” thick and 8” longer than the screen case dimension, with appropriate and rated mounting brackets.
Screen location must take into account viewing angles, the closest and furthest viewer, and minimize coverage of whiteboards. Refer to Appendix.
Screens must be installed according to manufacturer’s specifications and campus standards.
Any S-clip style mounting components must have a closing mechanism to prevent projector screen from jumping off of bracket.
Specified Product
Da-lite Advantage Model-C CSR or Approved Equal
Compliance
Comply with the following Codes and Industry Standards
American National Standards Institute (ANSI).
Electronics Industry Association (EIA).
Audio Engineering Society (AES).
National Electrical Code (NEC).
National Fire Protection Association (NFPA).
UL Compliance: Comply with requirements of UL 50.
California Building Code 2010
California Fire Code 2010
Building Industry Consulting Service International (BICSI)
Audiovisual and Integrated Experience Association (AVXIA)
Cal State Telecommunication and Infrastructure Performance standards (TIP)
Any other additional codes or regulations as identified by the AHJ
Installation Practices
Dedicated EMT conduit shall be installed when possible. In the situation where dedicated conduit runs are not viable , non-contiguous cable support mechanisms may be used. Non-contiguous cable support mechanisms such as hangers, rings, and hooks shall not be spaced farther than four (4) feet apart. All manufactured raceways used for cables shall be installed according to the raceway manufacturer’s specifications.
All above-tile plenum cables cannot lay against the ceiling tile and must be supported with dedicated hanging wire(s) and J-hooks.
Cable runs shall be supported with devices such as J-hooks designed for this purpose, and are to be installed independent of any other structural component.
Cables routed vertically up walls, or between floors as vertical riser, shall be supported with clamps or other mechanisms. These supports shall occur at least three times per floor.
Cable stapling of any recognized media type shall not be permitted.
Cables shall be dressed in conveniently sized bundles and either laced or banded. Lacing or banding shall not be so tight as to deform cable bundles.
Cabling installed with a bend radius less than that recommended by the cabling manufacturer is not acceptable.
Cables and bundles terminating at equipment or connector panels shall be supported so as not to put strain on connections or connectors.
All bulk cables shall be cut to the length dictated by the run. No splices shall be permitted in any pull boxes without prior approval of the Owner.
Cabling for equipment mounted in drawers or on slides shall be provided with a service loop of appropriate length. A cable management support for the service loop shall be provided to prevent the service loop travel from interfering with the operation of the drawer or slide, or snagging on adjacent cabling.
Wherever possible, m microphone level, line level, loudspeaker level and data cables shall each be run in separate conduits, trough, raceway divider, and cable bundles. Low voltage DC and control may be run along with any but microphone or line-level runs.
Termination
All termination components must meet or exceed all specifications for given media type and application as described in this document and system drawings. Cable service loops shall be provided.
Crimp-on connectors shall be installed only on the appropriate size cable using the manufacturer-recommended crimp tool and die set.
Connections to electronic devices providing screw terminals shall be terminated using the appropriate gauge insulated spade or ring crimp terminal connector and crimp tool.
All mechanical solder-on connectors shall be attached to cable ends using rosin core solder.
Audio signal cable shields shall be protected with the appropriate gauge Teflon or heat-shrinkable tubing. The jacket end of each audio cable shall be fitted with the appropriate gauge heat shrinkable tubing to provide additional protection to the base of the shield or shield foil. This also applies to the inside of mechanical connectors and cables that terminate at partitioned barrier strips.
Labeling
All cables shall be permanently identified at each end by machine-printed cable markers.
Every cable shall have a unique tag number identifier for each cable. The Contractor shall include this unique tag number on the As-Built signal flow documentation.
Cable markers shall be placed two (2) inches from where the cable exits the strain relief of the connector, but never within a cable bundle.
Cable labeling followings the AVIXA Standard, Cable Labeling for Audiovisual Systems, AVIXAF501.01:2015
Each cable marker shall include, in addition to the unique tag number identifier, the name of the origination and destination equipment termination at each cable end.
Specified Product
Impact Inc, Advanced Wire Marking System, LSL-78 or equivalent
Example of Existing Labelling
Updated Labeling to Match AVIXA Standards
Video Cable (Bulk)
CAT6A
Specifications
Cable for video should be HDB aseT (HDBT) certified CAT6 a , s solid conductor, 23 AWG, 4-pair, shielded, 625-MHz. Plenum-rated. Color: green, else black.
Specified Product
Infinity Cable ABA TSP2304503, ICE CAT6 a Plenum Shielded, or Approved Equal
CAT6A Connector
Specifications
CAT6A cables shall be terminated with shielded, modular keystone jacks ( Hubbell style) .
Specified Product
Hubbell PART# SJ6A or Approved Equal
Coaxial (single)
Specifications
Cable should be RG59/U, Plenum-rated, white.
Specified Product
ICE RG-59 HDTV Plenum
Video Cables (Patch)
HDMI User Cable
Specifications
HDMI Patch Cable should be at minimum HDMI 2.0 verified, 18 Gbps, CL3P certified, shielded, 24awg, gold plated connectors.
6 to 15 feet in length
Flexible PVC cable
Specified Product
Extron HDMI Ultra Series (length TBD) or Approved Equal
HDMI Patch Cable
Specifications
HDMI Patch Cable should be at minimum HDMI 2.0 verified , 1 8 Gbps, CL3P certified, shielded, 24awg, gold plated connectors.
Color: green, if available.
Specified Product
Comprehensive MICROFLEX Pro AV/IT Series High Speed HDMI 24 AWG with ProGrip, SureLength, CL2P Cable or Approved Equal, length TBD
Shielded CAT6 a (Video- HDBT)
Specifications
Shielded CAT6 a, Solid conductor, 24 AWG, 4-pair, 475-MHz. Terminated with shielded RJ-45 plugs.
Specified Product
Extron XTP DTP 24/n (length TBD) or Approved Equal
Audio & Control Cable (Bulk)
Loudspeaker cable
Specifications
Loudspeaker Cable is jacketed 16 AWG or 14 AWG, depending on amplifier wattage and cable length; shielded, and plenum-rated with overall jacket.
Specified Product
Belden Part# 6200UE; West Penn Part# 25225B or Approved Equal
Control & Audio Wire
Specifications
Cable is 22 AWG, shielded, twisted-pair, stranded, plenum-rated
Specified Product
Belden Part# 9451P or Approved Equal
Data Communication Cable
Bulk cable
Specifications
Data communication cable shall be Plenum-rated CAT6, 23awg, 4 Pr, Solid, 550mhz (w/spine), HDBaseT Certified, color blue.
Specified Product
Infinity Cable ABA TSP 2304503 or Approved Equal
Data Patch Cables
Specifications
Data patch cables shall be 23awg, 4 Pair, Stranded, Color blue with RJ45 connectors.
Length TBD
Specified Product
TBD
Final Audio-Visual equipment selection and system design shall be coordinated with campus representative.
Due to the rapidly changing technology horizon, standardized equipment and system design selections should be made as close to building commissioning as possible to ensure the most up-to-date technology is available.
Displays
LCD Projector
Specifications
Projector shall be a minimum of WUXGA (1920x1200) resolution, have an output of a minimum of 60 00 lumens and 2,500,000 000:1 contrast ratio.
Projector must have horizontal and vertical lens shift capabilities and security mount provision .
Projector shall use laser light source, rated to 20,000 hours.
Projector shall be networkable with message broadcasting capabilities and closed captioning.
Projector must offer at least two digital inputs (HDMI/DVI) , HDbaseT , and at least one of each of the following inputs: VGA, Composite Video, RS-232, RJ -45, WI - FI and USB.
Projector shall be equipped with Lens appropriate with mounting distance and screen size.
Projector shall be accompanied with appropriate accessories as needed: optional Wi-Fi adapter, extended warranty, & at least one spare lamp per projector.
Specified Product
EPSON Brand Laser Projector: L610U, L1100U/L1407U or Approved Equal [including part #’s V11H901020, V12H418P12 (WIFI adapter), and EPPEXPB2 (5 year warranty).
LCD Display
Specifications
OLED/LCD /LED/QLED TV shall have VESA mounting
Closed Captioning
Internal amplified speakers
Energy Star rated.
The display shall have the following inputs: VGA, HDMI, RS - 232, Ethernet, USB, PC Audio.
The display shall have analog and digital audio outputs.
Native resolution shall be 1920x1080 or greater with a minimum of 120Hz refresh rate.
If available, opt for a white bezel/frame
Specified Product
Samsung Brand Display: Part# UN( xx) RU7100 series or Approved Equal
Size of display must be equal to or greater than the AVIXA 2-D Display standards using 3% Element Height at the maximum distance in the Basic Decision Making model
Multiple displays may compensate for use of a smaller display, but it must follow the same AVIXA 2-D display standards @ 3% element height.
Projector Mounting Hardware
All mounts shall be installed according to manufacturer’s specifications and campus guidelines .
All mounts shall be seismically secured
Projector mount and mount adapter
Specifications
Mount shall provide a minimum of 4 anchor point to the projector and support up to 50 lbs with pitch, roll, and yaw adjustments.
Projector mount bracket shall be white or colored to match projector and mount pole.
Projector mount bracket shall have an integrated security locking mechanism with Campus-standard ‘Lock-C’ key .
Projector mount bracket shall be of a universal configuration, able to adapt to future projectors.
Specified Product
Chief Part# RPMC1W (Lock-C) or Approved Equal
Projector Extension Pole
Specifications
Projector mount pole [AKA: Adjustable extension column; Adjustable-height pipe adapter ] shall be 1.5 NPT threaded on both ends, contain cable exit points, security set screws, and be adjustable to meet ceiling height and projector needs.
Projector mount pole shall be able to support up to 500lbs.
Projector mount pole shall be white or of matching color to ceiling.
Length is to be determined per- installation but is typically sized to allow projector lens to be level with top-of-image.
Specified Product
Chief Part# CMS012018w or Approved Equal
Projector Wall Mount
Specifications
Projector wall mount shall be anchored to wall studs with a minimum of four anchor points.
Mount shall have integrated lateral shift, and telescoping extension.
Mount shall have a weight capacity of at least 15 0 lbs and structurally support 5x the weight of all components mounted onto mount (safe working load).
All mounts shall be installed according to manufacturer’s specifications and campus guidelines .
Specified Product
Chief Part# WMA2S or Approved Equal
Structural Ceiling Mount
Specifications
Projector ceiling mount shall be anchored to building structure with a minimum of four anchor points.
Mount shall have a rated weight capacity of at least 200 lbs and be UL certified, and be certified to hold 5 times the rated weigh t .
All mounts shall be installed according to manufacturer’s specifications and campus guidelines .
Bolts into ceiling must be a minimum rating of SAE 5 and may have to be procured separately .
Specified Product
Chief Part# CMA395, CMA330 or Approved Equal
Display Ceiling Mount for ‘T-Bar’ Ceiling Tile Replacement
Specifications
Projector ceiling mount shall be plenum-rated, full-tile false ceiling adapter with quick lock cables which replaces a 24 inch (610 mm) x 24 inch (610 mm) ceiling tile.
Mount shall feature two or more electrical and cable knockouts for running power or signal.
Accepts a 1.5 inch (38 mm) NPT pipe and uses wingnuts for rapid projector adjustments.
The mount also has the ability to shift the display or projector by 4 inches (102 mm) in any direction.
Specified Product
Premier Part# PP-FCMA-QL or Approved Equal
Large Screen Monitor Mounting Hardware
General Requirements
All mounting hardware shall be installed according to manufacture r’ s specifications and campus guidelines .
Any mounting hardware placed in hallways or a fire corridor must be fire rated (UL certified).
Mount must be UL certified to guarantee fire rating and being tested to four times the rated load limit .
The mount must also meet safe working load guidelines of being able to support five times the rated load limit.
Mount must be secured using SAE 5 bolts or greater
Wall-mounted Monitors and Mounts and associated mounted equipment with a total weight at or over 100lbs should have blocking board installed
On gypsum walls, the blocking board shall be placed behind gypsum board between studs to distribute weight as an added safety measure.
On Concrete Walls the blocking board can be installed on the finished surface of the wall. Board must be painted to match wall finish
Fixed Wall Mount
Specifications
Display mount bracket shall provide a minimum of 4 anchor points to wall studs and support up to a rated weight of 200 lbs.
Display mount bracket shall be of a universal configuration, able to adapt to future displays.
Specified Product
Chief Part# LSMU or Approved Equal
Articulating Wall Mount
Specifications
Display mount bracket shall provide a minimum of 4 anchor points to wall studs and support up to 200 lbs.
Mounting shall allow for extension from wall up to 37” and have a tilt/roll of - 15,+ 5-degree adjustments.
Mount bracket shall be of a universal configuration, able to adapt to future displays.
Specified Product
Chief Part# PDRU or Approved Equal
Desk Mount LCD Bracket
Specifications
Mounts onto a desk surface of at least 1" in thickness
Standard VESA 100 mount.
Multiple articulation points
Specified Product
Humanscale M8.1 or Ergotron Part# LX Monitor Arm or Approved Equal
Display Ceiling Mount for ‘T-Bar’ Ceiling Tile Replacement
Specifications
Display ceiling mount shall be plenum-rated, full-tile false ceiling adapter with quick lock cables which replaces a 24 inch (610 mm) x 24 inch (610 mm) ceiling tile.
Mount shall feature two or more electrical and cable knockouts for running power or signal.
Accepts a 1.5 inch (38 mm) NPT pipe and uses wingnuts for rapid projector adjustments.
The mount also has the ability to shift the display or projector by 4 inches (102 mm) in any direction.
All mounts shall be installed according to manufacturer’s specifications and campus guidelines .
Specified Product
Premier Part# PP-FCMA-QL or Approved Equal
Audio/Visual Equipment Rack
Cabinet Equipment Rack
Free-standing Equipment Rack
Specifications
Equipment Rack shall contain a minimum of 14 Rack Units (RU).
All rack rails shall be threaded for 10/32 screws.
All equipment components shall be rack mounted.
All rack components shall be secured with Security square-post truss-head screws, 3/4” long with washers (Middle Atlantic Part# HSK).
All racks shall have access to the back of rack, and access can be locked.
Refer to the Appendix below for typical rack layout.
Specified Product
Computer Comforts Part# IT-303036-SS or Approved Equal
Wall-mounted Equipment Rack
Specifications
Equipment Rack shall contain a minimum of 16 Rack Units (RU). All rack rails shall be threaded for 10/32 screws.
All equipment components shall be rack mounted.
All rack components shall be secured with Security square-post truss-head screws, 3/4” long with washers (Middle Atlantic HSK). Fully welded construction for strength.
Shall offer Tool-Free system for center section mounting
Center section swing shall be reversible and can be both key - locked and padlocked
Center section shall be keyed differently from optional front door for security
Optimized for passive thermal management
Specified Product
Middle Atlantic DWR and EWR series
Under Table Full Size Rack
Specifications
19" mounting EIA-310-D tapped 10-32 mounting rails
Horizontal or vertical equipment mounting
Rear cable access for cable management
Side cable access
6U rack
Specified Product
Proposed: Hammond Manufacturing VPB196UBK or Approved Equal
Rack Accessories
Most rack installations will require one of more of the following accessories:
Rack mount power distribution unit with 8 rear outlets. Specified Product: Tripplite PDUMH15net2LX
Rear rack mounting rails, tapped for 10-32 screws. Specified Product: Middle Atlantic Part# t.b.d.
Locking rear door. Key must be compatible with campus-standard Middle Atlantic products. Specified Product: Middle Atlantic Part# t.b.d.
Equipment shelves. Specified Product: Middle Atlantic Part# t.b.d.
Blank or vented rack panels. Specified Product: Middle Atlantic Part# t.b.d.
Loudspeakers
A number of variables determine how many ceiling speakers are required for proper coverage in a given application. Each environment is different based on the room dimensions and ambient noise. Consideration must be given to the listener height, audio program content, desired SPL - sound pressure level, and how much the client will tolerate sound pressure level variances throughout the space. Since speakers are often tailored for specific applications, their design and performance play a major role in determining quantities and positioning. Refer to Appendix below for essential loudspeaker formulas.
Drop Tile Ceiling Loudspeakers
Specifications
The Audio Speakers shall comply with the intelligibility requirement s set forth in NFPA 72-2010
Dual cone 8" drivers
Lay in-tile 2ft x 2ft dimensions
Can be tapped at 8Ohms, 4Ohms, 70V, or 100V operation
Frequency Range (-10 dB): 100 Hz – 16 kHz
Nominal Sensitivity: 96 dB
Nominal Coverage Angle: 100° conical coverage (ave. 1kHz - 4 kHz)
Specified Product
JBL Pro LCT 81C/T or Approved Equal
Wall Mounted Loudspeakers
Specifications
Wall-mounted loudspeaker shall be of an 8”, 2-Way design and use an integrated ball-mount
Loudspeakers may be either 8-Ohm or 70-Volt depending on amplifier used
Specified Product
JBL Part# Control-28 T-60 or Extron 725T or Approved Equal
Pendant Ceiling Speakers
Specifications
Specified Product
Audio Amplifiers
Small room Audio Amplifier (Cap < 70)
Specifications
Amplifier shall have a minimum output power rating of 20 Watts per channel @ 8 Ohms or 40 Watts, mono @ 70 Volts
Specified Product
Built into Extron IN1608xi IPCP SA (stereo amp)
Hall Research VSA-X21 HDBaseT Rx with Amp
Approved Equal
Mid range rooms (Cap > 70 and Cap < 150)
Specifications
Amplifier shall have a minimum output rating of 200 Watts RMS : 2 x 60 Watts per channel @ 8 Ohms or 200W @ 70V.
Outputs shall be bridgeable.
Must have automatic/configurable clip limiter and built-in compressor.
Amplifier shall be rack mountable and be ENERGY STAR qualified.
Specified Product
Extron Part# XPA 1002 (8 Ohm), XPA 1002-70 (70V) or Approved Equal
Large Room amplifiers (Cap 150+)
Specified Product
Crown DriveCore DCI series amplifier
Signal Distribution and Control System
AV Control Processor (Controller)
Specifications
A/V system hardware controller shall integrate with campus- standard help desk and system monitoring software:
Extron Global Viewer Enterprise
Controller shall have the following communication ports:
RS-232
Ethernet
Digital I/O
IR
Dry Contact Closure (Relays) .
SSH client/server communication capable
Controller must comply with all campus IT security standards.
All programming shall be turned over to the university and become property of the university with no limitation placed on its use.
Specified Product
Extron IPCP Pro 255 with Link License user interface Part # 60-1431-01A
AV User Interface (Touch Panel)
Specifications
A/V system hardware controller shall be controlled locally via a 7" touch panel appliance.
The touch panel should be able to accept an In-Common or equivalent certificate.
Touch screen shall be capable of being powered via PoE.
Touch Panel must comply with all campus IT security standards.
All UI design work and graphic images (vector images and raster images) shall be turned over to the university and become property of the university with no limitation placed on its use.
Specified Product
Extron TLP 725T or Approved Equal
AV Distribution Switcher/Scaler
Specifications
HDMI switcher shall be controllable via RS-232 control.
Switcher shall have a minimum of f our HDMI inputs .
Switcher shall be HDCP compliant.
Switcher shall have two simultaneous HDMI outputs.
Switcher shall have a fixed-level line output
Switcher shall have a variable-level line output
Switcher shall have a minimum of two analog balanced microphone inputs
Specified Product
Extron IN 1608xi -sa, IN 1808 -sa or Approved Equal
AV Distribution Amplifier (DA)
Specifications
HDMI Distribution amplifier (DA) via HDBaseT
The HDMI distribution amp shall offer 8 HDBaseT Certified outputs and one HDMI Loop output; PoH capability to power far-end receivers;
RS-232 & IR Pass-through
Shall have ability to control individuals devices via addressable ethernet ports
Specified Product
Extron Part # 60-1438-01 or Approved Equal
HDMI/ HDBaseT Extenders
Specifications
HDMI/ HDBaseT transmitters and receivers shall be remotely powered via PoE or PoH standards; shall include bi-directional RS-232 and IR signaling and be capable of ‘4K’ bandwidth.
The transmitter and receiver must be the same brand and compatible with each other (excluding final endpoints that have a built-in HDBaseT input) to minimize any hardware or chipset incompatibility issues.
Specified Products
Extron DTP TX HD2 230 or Approved Equal
Extron DTP RX 230 HDMI or Approved Equal
Input Wall Plate/Interface (‘BOB’)
Specifications
Audio– Visual active input interfaces shall be high-bandwidth, controllabl e via RS-232 control and shall have the following minimum inputs: (1) HDMI, (1) VGA, and Audio.
Interface shall be HDCP compliant and must have digital HDBaseT output and be powered by the receiver (PoE or PoH Standard).
Specified Product
Extron DTP T UWP 4K 232d, part # 60-1755-13 or Approved Equal
Wireless microphone system
Specifications
The wireless microphone system shall include a ‘belt pack’ style transmitter with lapel microphone and receiver ;
10 user-selectable frequencies, automatic frequency scan and Tone Lock squelch system for interference-free reception .
Must be compatible with and interchangeable with existing campus Audio- Technica audio systems with Frequency Band-I (482MHz - 507MHz).
Must meet all FCC guidelines and FCC acceptable frequency ranges for microphones
Specified Product
Audio-Technica Part# ATW-2129-I
Assisted Listening System (ALS)
Specifications
The Assisted Listening system shall be a network-based system that will allow end-users to connect to the system with mobile devices and launch an application to listen into the room’s audio stream .
Based on ADA rules and California Building Code, a minim um of two audio neck loops will be available for use with mobile devices , the number of neck loops required rises as seating capacity rises above 50 per room.
Refer to the Assisted Listening Systems section below.
Specified Product
Broadcast Vision Entertainment AudioFetch Express
Assisted Listening Microphone
Assisted Listening Microphone
Specifications
USB Connectivity
Acoustic Echo Cancelling Capability
Should utilize a beam forming microphone array
Specified Product
Acoustic Magic Voice Tracker II, or Nureva HDL300 or Approved Equal
Document Camera (Doc Cam)
Specifications
Minimum 13-megapixel resolution (4224x3156)
Must be capable of 1080P video @ 60FPS, 4K @ 30FPS
Must have a minimum of a 10x Mechanical Zoom, 8x Digital Zoom
Must have USB 3.0 Port
Traditional video output (HDMI) is optional
Specified Product
Hovercam Solo 8 Plus or Approved Equal
Power Distribution Units (26 27 33)
Related Articles
Request Support | 805-756-7000 | Service Catalog
Site Map | Privacy Notice | Web Accessibility Statement | © 2024 California Polytechnic State University